Critical vs non-critical defects in fire safety inspections

Last reviewed 25 October 2026 · Based on AS 1851-2012 (Amendment 1) and NSW guidance

AS 1851-2012 sorts what a routine service finds into three classes: critical defects, non-critical defects and non-conformances. The class decides who must be told and how quickly, and how urgently the owner needs to act. This page explains each class in plain language, with examples, and covers how to record them.

In short

The three classifications

The classifications are set out in clause 1.5.6 of AS 1851-2012, and the reporting requirements are in clause 1.17.1. This is a plain-language summary. Read the clauses themselves in your licensed copy.

ClassIn plain languageWhen the owner must hear about it
Critical defectThe system is out of action. If a fire broke out, people in the building, or in part of it, would likely be at serious risk.On site, before the technician leaves, or as soon as possible after. Then in writing within 24 hours, and again each time the same defect is found.
Non-critical defectA component is faulty or degraded, but it is not expected to stop the system working when needed.Within a week.
Non-conformanceThe system works, but something that routine servicing depends on is missing or wrong, such as design or baseline information.Within a week.

A routine service activity done outside its tolerance window is also recorded as a non-conformance (an "out-of-tolerance activity"). See tolerances.

Not the same as "critical fire safety measures"

In NSW, a critical fire safety measure is a Regulation term for a measure that the fire safety schedule says must be assessed more often than every 12 months. It triggers supplementary fire safety statements. A critical defect is an AS 1851-2012 term for a fault found during servicing. A critical measure can have no defects, and any measure can have a critical defect.

Deciding which class

Work through two questions, then apply the criteria in the relevant section of the standard and your own judgement:

  1. Is the system out of action, such that people would likely be at serious risk if a fire broke out? If yes, treat it as a critical defect.
  2. If not, is something actually faulty or degraded? If yes, it is a non-critical defect. If the system works but information is missing or wrong, or the work was out of tolerance, it is a non-conformance.

Some tests come with their own acceptance criteria. For example, the hydrant hydrostatic test method in the NSW good practice guide sets out when a result is a pass, a non-critical defect or a critical defect.

Who to tell, and how fast

The technician notifies the responsible entity, usually the building owner or their agent, on the timeframes above. Defects and their classifications also appear in the yearly condition report (clause 1.17.2). For a critical defect, don't stop at the conversation on site. Send the written confirmation within 24 hours, and reconfirm the defect each time it is found again until it is fixed.

What to do with each

Critical defect

Non-critical defect

Non-conformance

None of the official sources above sets a fixed rectification deadline for non-critical defects or non-conformances. Owners are expected to act in a timely way, guided by how serious the defect is.

Examples by measure

The examples marked "NSW guidance" come from Building Commission NSW material. The one marked "Illustration" simply applies the definition. Always classify against the standard's criteria and the building's design.

MeasureFindingClassBasis
Fire hydrant systemDuring the hydrostatic test, pressure drops rapidly (for example to 0 kPa or to town mains pressure) and the system will not hold pressure.CriticalNSW guidance (good practice guide, Appendix D)
Fire hydrant systemDuring the hydrostatic test, pressure falls steadily but the make-up water used is more than the allowance.Non-criticalNSW guidance (good practice guide, Appendix D)
Fire detection and alarmAfter a lightning strike, the fire indicator panel cannot be reset or repaired, leaving the systems it controls inoperative.CriticalNSW guidance (good practice guide, Appendix G, case study 1)
Fire pumpsetThe pumpset fails catastrophically during its annual load test.CriticalNSW guidance (good practice guide, Appendix G "Managing critical defects", case study 3)
Sprinkler, hydrant or pumpset systemsBaseline flow and pressure data from the original design is not available.Non-critical or Non-conformanceNSW guidance (owner responsibilities page): generally not a critical defect
Any measureA routine service activity is done outside its tolerance window.Non-conformanceNSW guidance (good practice guide); AS 1851-2012 clause 1.11
Automatic sprinkler systemThe main control valve is found shut, so no water reaches the installation.CriticalIllustration The system cannot operate.

Defects and the annual fire safety statement

In NSW, AS 1851 servicing is separate from the annual fire safety statement (AFSS), but the accredited practitioner may use AS 1851 results to inform their assessment. If critical defects may delay the statement, Building Commission NSW advises owners to tell the council immediately and work with it on a solution. See How to prepare an AFSS in NSW.

How to record defects well

The NSW good practice guide notes that under AS 1851-2012, every repair goes into the system's records, with the fault, what was done to fix it and the date of service. It also says logbook entries should reference the AS 1851 section and the interval, and that a hard copy stays on site. A useful defect record has:

NSW owners must keep AS 1851 records for at least 7 years and make them available for inspection. Authorities such as the council or Fire and Rescue NSW can ask to see the logbooks.

Log defects where you find them

Fire Toad is an iPhone app for fire safety practitioners. During a guided site inspection you can log a critical or non-critical defect against the measure, with photos and notes, and track it until it's rectified. Defects carry through to your branded inspection report. The offline toolkit includes a defect classifier to help you think the classification through, though the call is still yours. Everything stays on your phone, with no account needed.

Get Fire Toad on the App Store

Free to download, with your first 3 reports included. Fire Toad Pro, a monthly or yearly subscription, covers reports after that.

Sources

This page is general guidance, not legal advice. It summarises AS 1851-2012 in plain language and does not reproduce it. Classify defects against your licensed copy of the standard, the building's fire safety schedule and design, and your own professional judgement. Fire Toad is not affiliated with Standards Australia or the NSW Government.