How to prepare an Annual Fire Safety Statement (AFSS) in NSW

Last reviewed 25 October 2026 · For building owners, agents and accredited practitioners (fire safety)

An annual fire safety statement is the building owner's yearly declaration that an accredited practitioner (fire safety) has assessed every essential fire safety measure in the building and inspected its exits. This guide walks through who does what, the timing rules, the form and the lodgement, with a checklist at the end.

In short

Who is responsible

The requirements sit in Part 12 of the Environmental Planning and Assessment (Development Certification and Fire Safety) Regulation 2021 (the Regulation). They apply to owners of buildings that have essential fire safety measures. In practice these are usually buildings with a fire safety schedule (or, for some older buildings, an essential services list attached to an old approval or order), such as commercial, industrial, multi-unit residential and institutional buildings, but not houses.

When it is due

What the assessment involves

The owner's declaration (section 8 of the form) covers two things:

  1. Each essential fire safety measure has been assessed by an accredited practitioner (fire safety) as capable of performing to a standard no less than the one in the fire safety schedule. If the measure applies to the building but is not on the schedule, the benchmark is the standard it was originally designed and implemented to.
  2. The exits have been inspected by an accredited practitioner, and nothing found gave grounds for a prosecution under Part 15 of the Regulation. The inspection covers fire safety notices, fire exits, fire exit doors and the paths of travel to fire exits.

NSW Planning's FAQ notes that the assessment necessarily involves inspecting the measures in person at the property. Start from the building's current fire safety schedule. It lists each measure and its minimum standard of performance, and the statement must be accompanied by it.

How AS 1851-2012 maintenance fits in

From 13 February 2026, owners of class 1b and class 2 to 9 buildings in NSW must have their essential fire safety measures inspected, tested and maintained in accordance with AS 1851-2012, or to the standard in a relevant performance solution, where the standard covers the activity. Records must be kept for at least 7 years. Building Commission NSW says this routine servicing is separate from the AFSS. Not every AS 1851 item has to be completed before the statement is lodged, but the practitioner may use the AS 1851 results to inform their assessment. See AS 1851 routine service frequencies at a glance.

The accredited practitioner's role

The form

A fire safety statement must be in the form approved by the Planning Secretary. Version 4 of the template has been required since 1 September 2022 and is published on the NSW Planning fire safety certification page. Its sections are:

  1. Type of statement: annual or supplementary
  2. Description of the building or part
  3. Owner's name and address
  4. Fire safety measures: each measure, its minimum standard of performance, the date(s) assessed and the practitioner's accreditation number
  5. Inspection of fire exits and paths of travel (annual statements only)
  6. Name, contact details and signature of each accredited practitioner
  7. Details of the person making the declaration
  8. Annual statement declaration
  9. Supplementary statement declaration

Do not change the form. NSW Planning says adding or altering letterheads or logos, or adding or removing sections, may breach the Regulation. Put your branding on your assessment report, not on the statement.

New fire safety schedules have had to use the NSW Government's standard schedule template since 1 August 2023. If a building's schedule is missing or has errors, the owner can ask the council to reissue or correct it under section 80A.

Lodging and displaying it

Supplementary statements for critical measures

A critical fire safety measure is one the fire safety schedule says must be assessed at intervals of less than 12 months. It is also an essential measure, so it still appears on the annual statement.

Do not confuse the two uses of "critical". A critical fire safety measure is a Regulation term about how often a measure is assessed. A critical defect is an AS 1851-2012 term about a fault found during servicing. See Critical vs non-critical defects.

Late statements and penalties

Step by step

  1. Get the paperwork. Collect the current fire safety schedule, the last annual statement, any supplementary statement dates and the AS 1851 logbooks or yearly condition report. Confirm the due date with the council.
  2. Confirm who will declare. Identify the owner, or the agent and their written authority, and check they are independent of the practitioner(s).
  3. Match accreditation to the schedule. Check each practitioner's accreditation on the register covers every measure on the schedule and the exit inspection.
  4. Book the site visit. Schedule it inside the 3-month window, leaving time to fix defects before the due date.
  5. Assess on site. Assess each measure against its standard of performance on the schedule. Inspect the exits, fire exit doors, paths of travel and fire safety notices. Record dates, results, photos and defects.
  6. Deal with defects. Report critical defects to the owner straight away. A measure that is not capable of performing to its standard needs to be fixed and reassessed before the statement can cover it. If that will push the statement past its due date, talk to the council early.
  7. Complete the form. Use the unaltered version 4 template. List every measure with its standard, assessment date(s) and accreditation number. The practitioner signs section 6, or provides separate signed documents, and the owner or agent signs section 8.
  8. Lodge and display. Send it with the current schedule to the council and to Fire and Rescue NSW, and display both in the building.
  9. Diary the next dates. Note the next annual due date, any supplementary statements and the AS 1851 service intervals.

Checklist

Doing this on site? Fire Toad keeps it in one place

Fire Toad is an iPhone app for fire safety practitioners. You load the building's schedule and work through each measure on site (satisfactory, defect or N/A, with checklists, photos and notes), logging critical and non-critical defects as you go. It produces your branded inspection report, and it fills the official NSW AFSS template from the inspection, unaltered and without branding, with a readiness check. Everything stays on your phone, with no account. It is a record-keeping tool: the assessment and the declaration are still yours and the owner's.

Get Fire Toad on the App Store

Free to download, with your first 3 reports included. Fire Toad Pro, a monthly or yearly subscription, covers reports after that.

Sources

This page is general guidance for NSW, not legal advice. It summarises official sources as at the review date. Requirements and penalty amounts change, so check the current Regulation, the approved form and your local council before relying on it. Fire Toad is not affiliated with the NSW Government, Fire and Rescue NSW, Fire Protection Association Australia or Standards Australia.