AS 1851 routine service frequencies at a glance

Last reviewed 25 October 2026 · AS 1851-2012 incorporating Amendment 1 (2016)

AS 1851-2012 Routine service of fire protection systems and equipment covers the inspection, testing, preventive maintenance and survey of fire protection systems and equipment. This page lists the routine service intervals for common essential measures, by section and table number, so you can plan a year of servicing or check a contractor's program. It cites the standard and does not reproduce it, so read the activities themselves in your licensed copy.

The schedule and the edition govern

Why this matters in NSW now

From 13 February 2026, owners of new and existing class 1b and class 2 to 9 buildings in NSW must have their essential fire safety measures inspected and tested in accordance with AS 1851-2012, where the standard covers the activity. Councils enforce it. For existing buildings, Building Commission NSW says service intervals can start from 13 February 2026. It does not expect long-interval services, such as the 5-, 10- and 25-year activities, to all be done at once. It expects the first yearly service by February 2027.

Routine service intervals by measure

Intervals are taken from the service schedule headings in AS 1851-2012. Single items that run on a different interval come from the frequency matrix in the Building Commission NSW Good practice guide for implementing AS 1851-2012 (January 2026). Each schedule table lists the specific activities. Some items within a table run on a longer interval than the table's heading.

AS 1851-2012 routine service intervals (references are sections, clauses, tables and items in the standard)
MeasureRoutine service intervalsWhere to look
Water-based systems
Automatic fire sprinkler systems: wet pipeSection 2Monthly, six-monthly, yearly, then five-, ten-, twenty-five- and thirty-yearly2.4.2.1 to 2.4.2.4
Sprinklers: dry pipe, deluge and water spray, pre-actionSection 2Monthly, six-monthly, yearly, five-yearly2.4.3 to 2.4.5
Fire pumpsetsSection 3Monthly, six-monthly, yearly, five-yearly, plus one two-yearly item3.4.1 to 3.4.4; Table 3.4.3 item 3.5
Hose reel and pressure-maintenance (jacking) pumpsetsSection 3Monthly, six-monthly3.4.5
Fire hydrant systemsSection 4Monthly, six-monthly, yearly, five-yearly, plus a ten-yearly item. Hydrostatic testing applies where a fire brigade booster assembly is installed.4.4.1 to 4.4.4; Table 4.4.4 items 4.3 and 4.4(b)
Water storage tanks for fire protection systemsSection 5Monthly, six-monthly, yearly, ten-yearly, plus one six-yearly item5.4.1 to 5.4.4; Table 5.4.4 item 4.4
Delivery lay flat fire hoseSection 8Yearly8.4
Fire hose reelsSection 9Six-monthly, yearly9.4.1, 9.4.2
Detection, alarm and warning
Fire detection and alarm systemsSection 6Monthly, six-monthly, yearly, five-yearly, plus ten-yearly smoke detector sensitivity items6.4.1; Appendix G items G5 to G7
Smoke alarms and heat alarmsSection 6Six-monthly, yearly6.4.2
Emergency warning systemsSection 6Monthly, yearly, five-yearly6.4.3
Emergency intercom systemsSection 6Yearly6.4.4
Special hazard systemsSection 7Monthly, six-monthly, yearly, ten-yearly7.4.2 to 7.4.5
Portable equipment
Portable and wheeled fire extinguishersSection 10Six-monthly, yearly, five-yearly, plus a three-yearly activity10.4.1 to 10.4.3; clause 10.2.3
Fire blanketsSection 11Six-monthly11.4
Passive fire and smoke systems
Passive fire and smoke systemsSection 12Three-monthly, six-monthly and yearly activities depending on the component, plus one twenty-five-yearly item. Components include fire and smoke barriers and their penetrations, rated access panels and hatches, fire-protected structural members, fire-resistant doorsets, smoke doors, fire shutters, fire-rated glazing and fire-protected air ducts.12.4.1 to 12.4.7; Table 12.4.5 item 5.6(b)
Fire and smoke control features of mechanical services (Section 13)
Fire dampers and smoke dampersYearly, plus a twenty-five-yearly item13.4.1.4 and 13.4.2.9; Table 13.4.1.4 item 3.7
Fans and motorsThree-monthly, yearly13.4.1.2, 13.4.1.3
Automatic smoke and heat ventsSix-monthly, yearly, plus a twenty-five-yearly item13.4.1.9, 13.4.1.10; Table 13.4.1.10 item 9.14
Fire and smoke curtainsSix-monthly, yearly, plus a two-yearly item and a twenty-five-yearly item13.4.1.11, 13.4.1.12; Table 13.4.1.12 items 11.7 and 11.14
Motorised relief openings, windows and shuttersSix-monthly, yearly, plus a twenty-five-yearly item13.4.1.13, 13.4.1.14; Table 13.4.1.14 item 13.7
Fire-isolated exit pressurisation systemsThree-monthly, yearly13.4.2.2, 13.4.2.3
Smoke exhaust systemsThree-monthly, yearly13.4.2.6, 13.4.2.7
Kitchen exhaust systemsMonthly, yearly13.4.1.16, 13.4.1.17
Emergency planning
Emergency planning in facilitiesSection 14Six-monthly, yearly14.4.2, 14.4.3
Not covered by AS 1851-2012
Emergency lighting and exit signsNot covered by AS 1851-2012. Maintain to the standard in the fire safety schedule.Fire safety schedule

Section 13 also has components not listed here, such as air control dampers, variable frequency inverters and fire fan control panels. The NSW guide's matrix also shows five-yearly activities for that section. Check the full set of schedule tables in clause 13.4.

Tolerances and out-of-tolerance work

Clause 1.11 sets the frequencies (Table 1.11(A)) and a tolerance either side of each scheduled date (Table 1.11(B)). The tolerance runs from 5 working days for monthly activities and 10 working days for three-monthly activities, to 1 month for six-monthly and 2 months for yearly activities, and up to 6 months for the ten-, twenty-five- and thirty-yearly activities. The NSW guide explains that tolerances stop a year of "monthly" visits shrinking to eleven. An activity done outside its tolerance is recorded in the logbook as an out-of-tolerance activity and treated as a non-conformance. It should then be done as soon as practical.

Records you need to keep

AS 1851 servicing is separate from the NSW annual fire safety statement, but good records make the annual assessment easier. See How to prepare an AFSS in NSW.

Keep the intervals with the building

Fire Toad is an iPhone app for fire safety practitioners. Record each building's schedule, inspect measure by measure on site, log routine service activities against each measure, and see what's due. The offline toolkit includes a standards search by clause number and a measures directory. Your data stays on your phone, with no account needed.

Get Fire Toad on the App Store

Free to download, with your first 3 reports included. Fire Toad Pro, a monthly or yearly subscription, covers reports after that. Fire Toad cites standards by clause number with plain-language summaries and never reproduces them. Use your own licensed copy for the activities.

Sources

This page is general guidance, not legal advice, and it is not a substitute for AS 1851-2012. It lists intervals by section and table number only. The activities, criteria and exceptions are in the standard. The building's fire safety schedule, any performance solution and the edition your jurisdiction applies take precedence. Fire Toad is not affiliated with Standards Australia or the NSW Government.